| Dimensions and weight 3TC4417-0BP0 | |
|---|---|
| Weight | 0,7 kg |
| Height | 0 cm |
| Depth | 0 cm |
| Customs information 3TC4417-0BP0 | |
| The 3TC4417-0BP0 code is part of the PRODUCT GROUP , and of the GROUP CODE and of the PRODUCT CLASS | |
| SKU | 3TC44170BP0 |
| WEEE Take-Back Directive | In accordance with the WEEE Directive (2012/19/EU), the product is subject to the obligation of take-back at the end of its life. The manufacturer is responsible for the correct treatment and disposal of the industrial electronic product in accordance with current regulations. |
| 3TC4417-0BP0 Product step | |
| The 3TC4417-0BP0 Product is currently in production | |
The Siemens 3TC4417-0BP0 is a 3TC contactor designed for switching DC loads, in frame size 2, with 2 main poles normally open and a rated current of 32 A in utilization categories DC-3 and DC-5.
Unlike contactors for AC, 3TC contactors are built to reliably extinguish the electric arc that forms when switching direct current. Siemens describes them as compact, high-performance devices with high contact reliability and a particularly long switching endurance.
The main circuit has screw connection and, at 440 V, provides a rated operational current of 29 A and a rated operational power of 9 kW at DC-3/DC-5. The contactor is fitted with 2 NO + 2 NC auxiliary contacts for signalling and interlocking.
The coil is AC operated, with a rated voltage of 230/220 V AC at 50 Hz and 276/264 V AC at 60 Hz. The dimensions are approximately 70 x 85 x 104 mm (W x H x D) and the weight is approximately 0.68 kg.
3TC contactors are approved for worldwide use (e.g. IEC and UL/CSA). Arc chambers, solenoid coils and surge suppressors are available as accessories.
E-Repair offers a complete package of services focused on production continuity:
🚚 Product sales
✅ Standard 12-month warranty
The 3TC4417-0BP0 is specifically designed to switch DC loads in categories DC-3 and DC-5, where the electric arc is harder to extinguish. An AC contactor is not rated for this duty and must not be used in its place on DC circuits.
The main circuit is the same: size 2, 2 poles, 32 A and 2 NO + 2 NC auxiliary contacts. The coil is different: the 3TC4417-0BP0 is operated at 230 V AC 50 Hz / 277 V 60 Hz, the 3TC4417-0BL2 at 230 V AC 50/60 Hz and the 3TC4417-0AB4 at 24 V DC. When replacing, it is essential to choose the same control supply voltage.
Yes. For 3TC contactors, Siemens offers solenoid coils, arc chambers and surge suppressors as accessories. Before ordering, we recommend checking the Siemens catalogue for the correct spare part number for this size and control voltage.
The most frequent problems include worn or welded main contacts due to frequent switching under load, damaged arc chambers, coils burnt out by overvoltage or incorrect control voltage, humming caused by dirt on the magnet core surfaces and auxiliary contacts that do not switch correctly.
Yes. If available in stock, the contactor can be shipped quickly. Contact E-Repair Customer Care stating the part number and the control supply voltage of the installed contactor.
ℹ️ The information in this product sheet is general and indicative and may contain inaccuracies or errors. Before purchasing, installing or commissioning, always check the technical data in the manufacturer's official documentation or contact E-Repair.
E-Repair assumes no responsibility for the accuracy of this information. Always consult the manufacturer for the most up-to-date instructions and information.